Section 4
Protection functions
4.2.2
4.2.2.1
4.2.2.2
4.2.2.3
172
Technical revision
E
F
G
Directional earth-fault protection DEFxPDEF
Identification
Function description
Directional earth-fault protection, low
stage
Directional earth-fault protection, high
stage
Function block
A070433 V2 EN
Figure 74:
Function block
Functionality
The directional earth-fault protection function DEFxPDEF is used as directional
earth-fault protection for feeders.
The function starts and operates when the operating quantity (current) and polarizing
quantity (voltage) exceed the set limits and the angle between them is inside the set
operating sector. The operate time characteristic for low stage (DEFLPDEF) and high
stage (DEFHPDEF) can be selected to be either definite time (DT) or inverse definite
minimum time (IDMT).
In the DT mode, the function operates after a predefined operate time and resets when
the fault current disappears. The IDMT mode provides current-dependent timer
characteristics.
Change
Step value changed from 0.05 to 0.01 for the
multiplier setting
Internal improvement
Internal improvement
IEC 61850
IEC 60617
identification
identification
DEFLPDEF
Io> ->
DEFHPDEF
Io>> ->
1MRS757454 D
Time
ANSI/IEEE C37.2
device number
67N-1
67N-2
611 series
Technical Manual