Section 4
Protection functions
4.2.1.6
164
Table 152:
Measurement modes supported by EFxPTOC stages
Measurement mode
EFLPTOC
RMS
DFT
Peak-to-Peak
For a detailed description of the measurement modes, see the
Measurement modes

Timer characteristics

EFxPTOC supports both DT and IDMT characteristics. The user can select the timer
characteristics with the Operating curve type and Type of reset curve settings. When
the DT characteristic is selected, it is only affected by the Operate delay time and Reset
delay time settings.
The protection relay provides 16 IDMT characteristics curves, of which seven comply
with the IEEE C37.112 and six with the IEC 60255-3 standard. Two curves follow the
special characteristics of ABB praxis and are referred to as RI and RD. In addition to
this, a user programmable curve can be used if none of the standard curves are
applicable. The user can choose the DT characteristic by selecting the Operating
curve type values "ANSI Def. Time" or "IEC Def. Time". The functionality is
identical in both cases.
The following characteristics, which comply with the list in the IEC 61850-7-4
specification, indicate the characteristics supported by different stages:
Table 153:
Timer characteristics supported by different stages
Operating curve type
(1) ANSI Extremely Inverse
(2) ANSI Very Inverse
(3) ANSI Normal Inverse
(4) ANSI Moderately Inverse
(5) ANSI Definite Time
(6) Long Time Extremely Inverse
(7) Long Time Very Inverse
(8) Long Time Inverse
(9) IEC Normal Inverse
(10) IEC Very Inverse
(11) IEC Inverse
(12) IEC Extremely Inverse
(13) IEC Short Time Inverse
Table continues on next page
EFHPTOC
x
x
x
x
x
x
section in this manual.
EFLPTOC
x
x
x
x
x
x
x
x
x
x
x
x
x
1MRS757454 D
EFIPTOC
x
EFHPTOC
x
x
x
x
x
x