Parameter
Values (Range) Unit
Periodic trig
0...604 800
time
Stor. mode
0=Waveform
periodic
1=Trend /
cycle
Stor. mode
0=Waveform
manual
1=Trend /
cycle
Table 452:
RDRE Non-group channel settings
Parameter
Values (Range) Unit
Operation
1=on
5=off
Channel
0=Disabled
selection
1=Io
2=IL1
3=IL2
4=IL3
10=U1
11=U2
12=U3
14=U1B
17=CIo
1)
18=SI1
1)
19=SI2
20=SU0
1)
21=SU1
22=SU2
1)
26=SUoB
1)
27=SU1B
28=SU2B
1)
Channel id
0 to 64
text
characters,
alphanumeric
High trigger
0.00...60.00
level
Low trigger
0.00...2.00
level
Storage mode
0=Waveform
1=Trend /
cycle
1) Recordable values are available only in trend mode. In waveform mode, samples for this signal type are
constant zeroes. However, these signal types can be used to trigger the recorder on limit violations of
the corresponding analog channel.
Measurement functions
Step
s
10
1
1
Step
1
0
pu
0.01
pu
0.01
1
Section 7
Default
Description
0
Time between
periodic
triggerings
0
Storage mode
for periodic
triggering
0
Storage mode
for manual
triggering
Default
Description
1=on
Analog
channel is
enabled or
disabled
0=Disabled
Select the
signal to be
recorded by
this channel.
Applicable
values for this
parameter are
product
variant
dependent.
Every product
variant
includes only
the values that
are applicable
to that
particular
variant
DR analog
Identification
channel X
text for the
analog
channel used
in the
COMTRADE
format
10.00
High trigger
level for the
analog
channel
0.00
Low trigger
level for the
analog
channel
0
Storage mode
for the analog
channel
391

Advertisement

Table of Contents
loading

Table of Contents