Technical Data; Technical Revision History; Runtime Counter For Machines And Devices Mdsopt; Identification - ABB RELION 611 Series Technical Manual

Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

Section 6
Supervision functions
6.2.10
6.2.11
6.3
6.3.1
6.3.2
6.3.3
346

Technical data

Table 388:
HZCCxSPVC Technical data
Characteristic
Operation accuracy
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode

Technical revision history

Table 389:
HZCCxSPVC Technical revision history
Technical revision
B

Runtime counter for machines and devices MDSOPT

Identification

Function description
Runtime counter for machines and
devices

Function block

GUID-C20AF735-FF25-411B-9EA6-11D595484613 V3 EN
Figure 170:
Function block

Functionality

The runtime counter for machines and devices function MDSOPT calculates and
presents the accumulated operation time of a machine or device as the output. The unit
of time for accumulation is hour. The function generates a warning and an alarm when
Value
Depending on the frequency of the current
measured: f
±2 Hz
n
±1.5% of the set value or ±0.002 × I
<40 ms
Typically 0.96
<35 ms
±1.0% of the set value or ±20 ms
Change
Function name changed from HZCCRDIF to
HZCCASPVC, HZCCBSPVC, HZCCCSPVC.
IEC 61850
IEC 60617
identification
identification
MDSOPT
OPTS
1MRS757454 D
n
ANSI/IEEE C37.2
device number
OPTM
611 series
Technical Manual