Section 13
Protection relay and functionality tests
518
Description
Pulse magnetic field immunity
test
Damped oscillatory magnetic
field immunity test
•
2 s
•
1 MHz
Voltage dips and short
interruptions
Power frequency immunity test
•
Common mode
•
Differential mode
Conducted common mode
disturbances
Emission tests
•
Conducted
0.15...0.50 MHz
0.5...30 MHz
•
Radiated
30...230 MHz
230...1000 MHz
1...3 GHz
3...6 GHz
Type test value
1000 A/m
6.4/16 µs
100 A/m
400 transients/s
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
Binary inputs only
300 V rms
150 V rms
15 Hz...150 kHz
Test level 3 (10/1/10 V rms)
<79 dB (µV) quasi peak
<66 dB (µV) average
<73 dB (µV) quasi peak
<60 dB (µV) average
<40 dB (µV/m) quasi peak,
measured at 10 m distance
<47 dB (µV/m) quasi peak,
measured at 10 m distance
<76 dB (µV/m) peak
<56 dB (µV/m) average,
measured at 3 m distance
<80 dB (µV/m) peak
<60 dB (µV/m) average,
measured at 3 m distance
1MRS757454 D
Reference
IEC 61000-4-9
IEC 61000-4-10
IEC 61000-4-11
IEC 61000-4-16
IEC 60255-26, class A
IEC 61000-4-16
EN 55011, class A
IEC 60255-26
CISPR 11
CISPR 12
611 series
Technical Manual