Section 13
Protection relay and functionality tests
518
Description
Pulse magnetic field immunity
test
Damped oscillatory magnetic
field immunity test
2 s
1 MHz
Voltage dips and short
interruptions
Power frequency immunity test
Common mode
Differential mode
Conducted common mode
disturbances
Emission tests
Conducted
0.15...0.50 MHz
0.5...30 MHz
Radiated
30...230 MHz
230...1000 MHz
1...3 GHz
3...6 GHz
Type test value
1000 A/m
6.4/16 µs
100 A/m
400 transients/s
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
Binary inputs only
300 V rms
150 V rms
15 Hz...150 kHz
Test level 3 (10/1/10 V rms)
<79 dB (µV) quasi peak
<66 dB (µV) average
<73 dB (µV) quasi peak
<60 dB (µV) average
<40 dB (µV/m) quasi peak,
measured at 10 m distance
<47 dB (µV/m) quasi peak,
measured at 10 m distance
<76 dB (µV/m) peak
<56 dB (µV/m) average,
measured at 3 m distance
<80 dB (µV/m) peak
<60 dB (µV/m) average,
measured at 3 m distance
1MRS757454 D
Reference
IEC 61000-4-9
IEC 61000-4-10
IEC 61000-4-11
IEC 61000-4-16
IEC 60255-26, class A
IEC 61000-4-16
EN 55011, class A
IEC 60255-26
CISPR 11
CISPR 12
611 series