Monitored data

Table 262:
MNSPTOC Monitored data
Name
Type
START_DUR
FLOAT32
T_ENARESTART
INT32
MNSPTOC
Enum

Technical data

Table 263:
MNSPTOC Technical data
Characteristic
Operation accuracy
1)2)
Start time
I
Fault
value
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Operate time accuracy in inverse time mode
Suppression of harmonics
1) Negative-sequence current before = 0.0, f
measurements
2) Includes the delay of the signal output contact
Start value multiples in range of 1.10...5.00
3)

Technical revision history

Table 264:
MNSPTOC Technical revision history
Technical revision
B
C
Values (Range)
Unit
0.00...100.00
%
0...10000
s
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Depending on the frequency of the measured
current: f
±1.5% of the set value or ±0.002 × I
Minimum
Start
= 2.0 × set
23
Typically 40 ms
Typically 0.96
<35 ms
±1.0% of the set value or ±20 ms
±5.0% of the theoretical value or ±20 ms
DFT: -50 dB at f = n × f
= 50 Hz, results based on statistical distribution of 1000
n
Change
Internal improvement
Internal improvement
Section 4
Protection functions
Description
Ratio of start time /
operate time
Estimated time to reset of
block restart
Status
±2 Hz
n
n
Typical
Maximum
25 ms
28 ms
, where n = 2, 3, 4, 5,...