ABB RELION 611 Series Technical Manual page 525

Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

1MRS757454 D
611 series
Technical Manual
Table 504:
Insulation tests
Description
Dielectric tests
Impulse voltage test
Insulation resistance
measurements
Protective bonding resistance
Table 505:
Mechanical tests
Description
Vibration tests (sinusoidal)
Shock and bump test
Seismic test
Table 506:
Environmental tests
Description
Dry heat test
Dry cold test
Damp heat test
Change of temperature test
Storage test
1) For relays with an LC communication interface the maximum operating temperature is +70
Table 507:
Product safety
Description
LV directive
Standard
Protection relay and functionality tests
Type test value
2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min,
communication
5 kV, 1.2/50 μs, 0.5 J
1 kV, 1.2/50 μs, 0.5 J,
communication
>100 MΩ, 500 V DC
<0.1 Ω, 4 A, 60 s
Requirement
Class 2
Class 2
Class 2
Type test value
96 h at +55ºC
16 h at +85ºC
1)
96 h at -25ºC
16 h at -40ºC
6 cycles (12 h + 12 h) at
+25°C...+55°C, humidity
>93%
5 cycles (3 h + 3 h)
at -25°C...+55°C
96 h at -40ºC
96 h at +85ºC
Reference
2006/95/EC
EN 60255-27 (2013)
EN 60255-1 (2009)
Section 13
Reference
IEC 60255-27
IEC 60255-27
IEC 60255-27
IEC 60255-27
Reference
IEC 60068-2-6 (test Fc)
IEC 60255-21-1
IEC 60068-2-27 (test Ea shock)
IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2
IEC 60255-21-3
Reference
IEC 60068-2-2
IEC 60068-2-1
IEC 60068-2-30
IEC60068-2-14
IEC 60068-2-1
IEC 60068-2-2
o
C
519