Signals; Settings - ABB RELION 611 Series Technical Manual

Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

1MRS757454 D
5.5.6
5.5.7
Table 361:
CBPSOF Group settings (Basic)
Parameter
Values (Range)
Operate delay time
Table 362:
CBPSOF Group settings (Advanced)
Parameter
Values (Range)
SOTF reset time
Table 363:
CBPSOF Non group settings (Basic)
Parameter
Values (Range)
Operation
611 series
Technical Manual
The overcurrent high and instantaneous signals, for example, the PHIPTOC START
signal is connected to the function START input. When the SOTF control module is
active and the START input is activated, the function operates instantaneously without
any delays.
The overcurrent low stage signals, for example, PHLPTOC START signal is
connected to the function START_DLYD input. The setting parameter Operate delay
time is used to delay the operation in case of inrush situation.

Signals

Table 359:
CBPSOF Input signals
Name
START
START_DLYD
CB_CL_CMD
BLOCK
Table 360:
CBPSOF Output signals
Name
OPERATE

Settings

Unit
0...60000
ms
Unit
0...60000
ms
Unit
1=on
5=off
Type
Default
Description
BOOLEAN
0=False
Start from function to be accelerated by SOTF
BOOLEAN
0=False
Start from function to be accelerated with delay by
SOTF
BOOLEAN
0=False
External enabling of SOTF by CB close command
BOOLEAN
0=False
Block of function
Type
Description
BOOLEAN
Operate
Step
Default
1
0
Step
Default
1
1000
Step
Default
1=on
Protection related functions
Description
Time delay for start input
Description
SOTF detection period after initialization
Description
Operation Off / On
Section 5
327