Calculated measurements
Calculated residual current and voltage
The residual current is calculated from the phase currents according to equation:
(
)
Io
I
I
I
= −
A
+
B
+
C
GUID-B9280304-8AC0-40A5-8140-2F00C1F36A9E V1 EN
The residual voltage is calculated from the phase-to-earth voltages when the VT
connection is selected as "Wye" with the equation:
Uo
(
U
U
U
) / 3
A
B
C
=
+
+
GUID-03909E83-8AA3-42FF-B088-F216BBB16839 V1 EN
Sequence components
The phase-sequence current components are calculated from the phase currents
according to:
I
(
I
I
I
) /
3
0
=
A
+
B
+
C
GUID-2319C34C-8CC3-400C-8409-7E68ACA4F435 V2 EN
2
I
(
I
a I
a
I
1
A
B
C
=
+ ⋅
+
GUID-02E717A9-A58F-41B3-8813-EB8CDB78CBF1 V2 EN
2
I
(
I
a
I
a I
2
A
B
C
=
+
+ ⋅
GUID-80F92D60-0425-4F1F-9B18-DB2DEF4C2407 V2 EN
The phase-sequence voltage components are calculated from the phase-to-earth
voltages when VT connection is selected as "Wye" with the equations:
U
(
U
U
U
) /
3
0
=
A
+
B
+
C
GUID-49CFB460-5B74-43A6-A72C-AAD3AF795716 V2 EN
2
U
(
U
a U
a U
1
A
B
=
+ ⋅
+
GUID-7A6B6AAD-8DDC-4663-A72F-A3715BF3E56A V2 EN
2
U
(
U
a U
a U
2
=
A
+
B
+ ⋅
GUID-6FAAFCC1-AF25-4A0A-8D9B-FC2FD0BCFB21 V1 EN
When VT connection is selected as "Delta", the positive and negative phase sequence
voltage components are calculated from the phase-to-phase voltages according to the
equations:
2
U
(
U
a U
) /
3
1
=
AB
BC
GUID-70796339-C68A-4D4B-8C10-A966BD7F090C V2 EN
U
(
U
a U
) /
3
2
=
AB
− ⋅
BC
GUID-C132C6CA-B5F9-4DC1-94AF-FF22D2F0F12A V2 EN
General function block features
) /
3
) /
3
) /
3
C
) /
3
C
Section 9
(Equation 51)
(Equation 52)
(Equation 53)
(Equation 54)
(Equation 55)
(Equation 56)
(Equation 57)
(Equation 58)
(Equation 59)
(Equation 60)