Signals; Settings - ABB RELION 611 Series Technical Manual

Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

Section 7
Measurement functions
7.1.5.3
7.1.5.4
Table 410:
VMMXU Non group settings (Basic)
Parameter
Operation
Num of phases
V high high limit
V high limit
V low limit
V low low limit
V deadband
Table 411:
VMMXU Non group settings (Advanced)
Parameter
Measurement mode
364

Signals

Table 408:
VMMXU Input signals
Name
U_A_AB
U_B_BC
U_C_CA
BLOCK
Table 409:
VMMXU Output signals
Name
HIGH_ALARM
HIGH_WARN
LOW_WARN
LOW_ALARM

Settings

Values (Range)
Unit
1=on
5=off
1=1 out of 3
2=2 out of 3
3=3 out of 3
0.00...4.00
xUn
0.00...4.00
xUn
0.00...4.00
xUn
0.00...4.00
xUn
100...100000
Values (Range)
Unit
1=RMS
2=DFT
Type
Default
Description
SIGNAL
0
Phase to earth voltage A or phase to phase voltage
AB
SIGNAL
0
Phase to earth voltage B or phase to phase voltage
BC
SIGNAL
0
Phase to earth voltage C or phase to phase voltage
CA
BOOLEAN
0=False
Block signal for all binary outputs
Type
Description
BOOLEAN
High alarm
BOOLEAN
High warning
BOOLEAN
Low warning
BOOLEAN
Low alarm
Step
Default
1=on
1=1 out of 3
1
1.40
1
1.20
1
0.00
1
0.00
1
10000
Step
Default
2=DFT
1MRS757454 D
Description
Operation Off / On
Number of phases required by limit
supervision
High alarm voltage limit
High warning voltage limit
Low warning voltage limit
Low alarm voltage limit
Deadband configuration value for integral
calculation. (percentage of difference
between min and max as 0,001 % s)
Description
Selects used measurement mode
Technical Manual
611 series