Figure 165:
Incorrect connection of trip-circuit supervision
A connection of three protection relays with a double pole trip circuit is shown in the
following figure. Only the protection relay R3 has an internal TCS circuit. In order to
test the operation of the protection relay R2, but not to trip the circuit breaker, the
upper trip contact of the protection relay R2 is disconnected, as shown in the figure,
while the lower contact is still connected. When the protection relay R2 operates, the
coil current starts to flow through the internal resistor of the protection relay R3 and
the resistor burns immediately. As proven with the previous examples, both trip
contacts must operate together. Attention should also be paid for correct usage of the
trip-circuit supervision while, for example, testing the protection relay.
Section 6
Supervision functions
337