Signals; Settings; Monitored Data - ABB RELION 611 Series Technical Manual

Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

1MRS757454 D
5.3.6
5.3.7
Table 349:
TRPPTRC Non group settings (Basic)
Parameter
Values (Range)
Operation
Trip pulse time
Trip output mode
5.3.8
611 series
Technical Manual

Signals

Table 347:
TRPPTRC Input signals
Name
BLOCK
OPERATE
RST_LKOUT
Table 348:
TRPPTRC Output signals
Name
TRIP
CL_LKOUT

Settings

Unit
1=on
5=off
20...60000
ms
1=Non-latched
2=Latched
3=Lockout

Monitored data

Table 350:
TRPPTRC Monitored data
Name
TRPPTRC
Type
Default
Description
BOOLEAN
0=False
Block of function
BOOLEAN
0=False
Operate
BOOLEAN
0=False
Input for resetting the circuit breaker lockout
function
Type
Description
BOOLEAN
General trip output signal
BOOLEAN
Circuit breaker lockout output (set until reset)
Step
Default
1=on
1
250
1=Non-latched
Type
Values (Range)
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Protection related functions
Description
Operation Off / On
Minimum duration of trip output signal
Select the operation mode for trip output
Unit
Description
Status
Section 5
321