Function Block; Signals; Settings - ABB RELION 611 Series Technical Manual

Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

1MRS757454 D
7.1.10.2
7.1.10.3
7.1.10.4
Table 441:
VSMSQI Non group settings (Basic)
Parameter
Values (Range)
Operation
Ps Seq V Hi high Lim
Ps Seq V high limit
Ps Seq V low limit
Ps Seq V low low Lim
Ps Seq V deadband
Ng Seq V Hi high Lim
Ng Seq V High limit
Ng Seq V low limit
Ng Seq V low low Lim
Ng Seq V deadband
Table continues on next page
611 series
Technical Manual

Function block

GUID-63393283-E2C1-406A-9E70-847662D83CFC V2 EN
Figure 181:
Function block

Signals

Table 440:
VSMSQI Input signals
Name
U
0
U
1
U
2

Settings

Unit
1=on
5=off
0.00...4.00
xUn
0.00...4.00
xUn
0.00...4.00
xUn
0.00...4.00
xUn
100...100000
0.00...4.00
xUn
0.00...4.00
xUn
0.00...4.00
xUn
0.00...4.00
xUn
100...100000
Type
Default
Description
SIGNAL
0
Zero sequence voltage
SIGNAL
0
Positive phase sequence voltage
SIGNAL
0
Negative phase sequence voltage
Step
Default
1=on
1
1.40
1
1.20
1
0.00
1
0.00
1
10000
1
0.20
1
0.05
1
0.00
1
0.00
1
10000
Section 7
Measurement functions
Description
Operation Off / On
High alarm voltage limit for positive
sequence voltage
High warning voltage limit for positive
sequence voltage
Low warning voltage limit for positive
sequence voltage
Low alarm voltage limit for positive
sequence voltage
Deadband configuration value for positive
sequence voltage for integral calculation.
(percentage of difference between min
and max as 0,001 % s)
High alarm voltage limit for negative
sequence voltage
High warning voltage limit for negative
sequence voltage
Low warning voltage limit for negative
sequence voltage
Low alarm voltage limit for negative
sequence voltage
Deadband configuration value for
negative sequence voltage for integral
calculation. (percentage of difference
between min and max as 0,001 % s)
377

Advertisement

Table of Contents
loading

Table of Contents