Section 4
Protection functions
292
GUID-DDAD7B3F-28BE-4573-BE79-FBB488A22ECA V1 EN
GUID-1470A4DB-310F-46BC-B775-843EAB8BA836 V1 EN
Figure 137:
Functionality of start-up supervision in the "IIt, CB" mode and the "IIt
and stall, CB" mode
The Str over delay time setting has different purposes in different modes of operation.
In the "IIt" or "IIt & stall" modes, the aim of this setting is to check for the
completion of the motor start-up period. The purpose of this time delay setting is
to allow for short interruptions in the current without changing the state of the
MOT_START output. In this mode of operation, the value of the setting is in the
range of around 100 milliseconds.
In the "IIt, CB" or "IIt & stall, CB" modes, the purpose of this setting is to check
for the life of the protection scheme after the CB_CLOSED input has been
activated. Based on the values of the phase currents, the completion of the start-
up period cannot be judged. So in this mode of operation, the value of the time
1MRS757454 D
611 series
Technical Manual