Section 4
Protection functions
Table 306:
PSPTUV Group settings (Advanced)
Parameter
Voltage block value
Enable block value
Table 307:
PSPTUV Non group settings (Basic)
Parameter
Operation
Table 308:
PSPTUV Non group settings (Advanced)
Parameter
Reset delay time
Relative hysteresis
4.5.5.8
4.5.5.9
280
Values (Range)
Unit
0.01...1.00
xUn
0=False
1=True
Values (Range)
Unit
1=on
5=off
Values (Range)
Unit
0...60000
ms
1.0...5.0
%

Monitored data

Table 309:
PSPTUV Monitored data
Name
START_DUR
PSPTUV

Technical data

Table 310:
PSPTUV Technical data
Characteristic
Operation accuracy
1)2)
Start time
Reset time
Reset ratio
Table continues on next page
Step
Default
0.01
0.20
1=True
Step
Default
1=on
Step
Default
1
20
0.1
4.0
Type
Values (Range)
FLOAT32
0.00...100.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Depending on the frequency of the measured
voltage: f
±1.5% of the set value or ±0.002 × U
Minimum
Start
U
= 0.99 × set
52 ms
Fault
value
44 ms
Start
U
= 0.9 × set
Fault
value
Typically 40 ms
Depends on the set
1MRS757454 D
Description
Internal blocking level
Enable Internal Blocking
Description
Operation Off / On
Description
Reset delay time
Relative hysteresis for operation
Unit
Description
%
Ratio of start time /
operate time
Status
±2 Hz
n
Typical
Maximum
55 ms
58 ms
47 ms
50 ms
Relative hysteresis
Technical Manual
n
611 series