Section 4
Protection functions
Parameter
Curve parameter B
Curve parameter C
Curve parameter D
Curve parameter E
Table 108:
DPHLPDOC Non group settings (Advanced)
Parameter
Minimum operate time
Reset delay time
Measurement mode
Allow Non Dir
Min operate current
Min operate voltage
Table 109:
DPHHPDOC Group settings (Basic)
Parameter
Start value
Start value Mult
Directional mode
Time multiplier
Operating curve type
Operate delay time
Characteristic angle
Max forward angle
Max reverse angle
Min forward angle
Min reverse angle
126
Values (Range)
Unit
0.0000...0.7120
0.02...2.00
0.46...30.00
0.0...1.0
Values (Range)
Unit
20...60000
ms
0...60000
ms
1=RMS
2=DFT
3=Peak-to-Peak
0=False
1=True
0.01...1.00
xIn
0.01...1.00
xUn
Values (Range)
Unit
0.10...40.00
xIn
0.8...10.0
1=Non-directional
2=Forward
3=Reverse
0.05...15.00
1=ANSI Ext. inv.
3=ANSI Norm. inv.
5=ANSI Def. Time
9=IEC Norm. inv.
10=IEC Very inv.
12=IEC Ext. inv.
15=IEC Def. Time
17=Programmable
40...200000
ms
-179...180
deg
0...90
deg
0...90
deg
0...90
deg
0...90
deg
Step
Default
1
0.1217
1
2.00
1
29.10
1
1.0
Step
Default
1
20
1
20
2=DFT
0=False
0.01
0.01
0.01
0.01
Step
Default
0.01
0.10
0.1
1.0
2=Forward
0.01
1.00
15=IEC Def. Time
10
40
1
60
1
80
1
80
1
80
1
80
1MRS757454 D
Description
Parameter B for customer programmable
curve
Parameter C for customer programmable
curve
Parameter D for customer programmable
curve
Parameter E for customer programmable
curve
Description
Minimum operate time for IDMT curves
Reset delay time
Selects used measurement mode
Allows prot activation as non-dir when dir
info is invalid
Minimum operating current
Minimum operating voltage
Description
Start value
Multiplier for scaling the start value
Directional mode
Time multiplier in IEC/ANSI IDMT curves
Selection of time delay curve type
Operate delay time
Characteristic angle
Maximum phase angle in forward
direction
Maximum phase angle in reverse
direction
Minimum phase angle in forward direction
Minimum phase angle in reverse direction
Technical Manual
611 series

Advertisement

Table of Contents
loading

Table of Contents