611 series
Technical Manual
Technical data
Table 357:
ESMGAPC Technical data
Characteristic
Operation accuracy
Technical revision history
Table 358:
ESMGAPC Technical revision history
Technical revision
B
C
Switch onto fault CBPSOF
Identification
Function description
Switch onto fault
Function block
GUID-5F45AD47-0FF7-47EC-B360-7F0F5F97E7F8 V1 EN
Figure 156:
Function block
Functionality
The switch onto fault function CBPSOF provides an instantaneous trip or a time
delayed trip when closing the breaker while a fault exists.
CBPSOF is activated when the CB_CL_CMD circuit breaker closing command is set
high. The function has START and START_DLYD inputs for immediate or delayed
start operation respectively.
Protection related functions
Value
At the frequency f = f
±1.5% of the set value or ±0.002 × U
Change
Internal improvement
Internal improvement
IEC 61850
IEC 60617
identification
identification
CBPSOF
SOTF
Section 5
n
n
ANSI/IEEE C37.2
device number
SOTF
325