Monitored Data - ABB RELION 611 Series Technical Manual

Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

Section 4
Protection functions
Parameter
Maximum temperature
Alarm value
Reclose temperature
Table 121:
T1PTTR Group settings (Advanced)
Parameter
Current multiplier
Table 122:
T1PTTR Non group settings (Basic)
Parameter
Operation
Table 123:
T1PTTR Non group settings (Advanced)
Parameter
Initial temperature
4.1.3.8
136
Values (Range)
Unit
20.0...200.0
°C
20.0...150.0
°C
20.0...150.0
°C
Values (Range)
Unit
1...5
Values (Range)
Unit
1=on
5=off
Values (Range)
Unit
-50.0...100.0
°C

Monitored data

Table 124:
T1PTTR Monitored data
Name
TEMP
TEMP_RL
T_OPERATE
T_ENA_CLOSE
TEMP_AMB
T1PTTR
Step
Default
0.1
90.0
0.1
80.0
0.1
70.0
Step
Default
1
1
Step
Default
1=on
Step
Default
0.1
0.0
Type
Values (Range)
FLOAT32
-100.0...9999.9
FLOAT32
0.00...99.99
INT32
0...60000
INT32
0...60000
FLOAT32
-99...999
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
1MRS757454 D
Description
Temperature level for operate
Temperature level for start (alarm)
Temperature for reset of block reclose
after operate
Description
Current multiplier when function is used
for parallel lines
Description
Operation Off / On
Description
Temperature raise above ambient
temperature at startup
Unit
Description
°C
The calculated
temperature of the
protected object
The calculated
temperature of the
protected object relative
to the operate level
s
Estimated time to operate
s
Estimated time to
deactivate BLK_CLOSE
°C
The ambient temperature
used in the calculation
Status
Technical Manual
611 series