Operation Principle - ABB RELION 611 Series Technical Manual

Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

1MRS757454 D
4.5.4.4
611 series
Technical Manual

Operation principle

The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of NSPTOV can be described using a module diagram. All the modules
in the diagram are explained in the next sections.
GUID-0014077D-EEA8-4781-AAC7-AFDBAAF415F4 V1 EN
Figure 129:
Functional module diagram
Level detector
The calculated negative-sequence voltage is compared to the set Start value setting. If
the value exceeds the set Start value, the level detector enables the timer.
Timer
Once activated, the timer activates the START output. The time characteristic is
according to DT. When the operation timer has reached the value set by Operate delay
time, the OPERATE output is activated if the overvoltage condition persists. If the
negative-sequence voltage normalizes before the module operates, the reset timer is
activated. If the reset timer reaches the value set by Reset delay time, the operate timer
resets and the START output is deactivated.
The timer calculates the start duration value START_DUR, which indicates the
percentage ratio of the start situation and the set operation time. The value is available
in the monitored data view.
Blocking logic
There are three operation modes in the blocking function. The operation modes are
controlled by the BLOCK input and the global setting in Configuration/System/
Blocking mode which selects the blocking mode. The BLOCK input can be controlled
by a binary input, a horizontal communication input or an internal signal of the
protection relay's program. The influence of the BLOCK signal activation is
preselected with the global setting Blocking mode.
The Blocking mode setting has three blocking methods. In the "Freeze timers" mode,
the operation timer is frozen to the prevailing value, but the OPERATE output is not
deactivated when blocking is activated. In the "Block all" mode, the whole function is
blocked and the timers are reset. In the "Block OPERATE output" mode, the function
operates normally but the OPERATE output is not activated.
Section 4
Protection functions
273