ABB RELION 611 Series Technical Manual page 57

Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

1MRS757454 D
611 series
Technical Manual
Each LED is seen in the Application Configuration tool as an individual function
block. Each LED has user-editable description text for event description. The state
("None", "OK", "Alarm") of each LED can also be read under a common monitored
data view for programmable LEDs.
The LED status also provides a means for resetting the individual LED via
communication. The LED can also be reset from configuration with the RESET input.
The resetting and clearing function for all LEDs is under the Clear menu.
The menu structure for the programmable LEDs is presented in
common color selection setting Alarm colour for all ALARM inputs is in the General
menu, while the LED-specific settings are under the LED-specific menu nodes.
Programmable LEDs
GUID-0DED5640-4F67-4112-9A54-E8CAADFFE547 V1 EN
Figure 13:
Menu structure
Alarm mode alternatives
The ALARM input behavior can be selected with the alarm mode settings from the
alternatives "Follow-S", "Follow-F", "Latched-S" and "LatchedAck-F-S". The OK
input behavior is always according to "Follow-S". The alarm input latched modes can
be cleared with the reset input in the application logic.
GUID-58B6C3F2-873A-4B13-9834-9BB21FCA5704 V1 EN
Figure 14:
Symbols used in the sequence diagrams
"Follow-S": Follow Signal, ON
In this mode ALARM follows the input signal value, Non-latched.
General
Alarm color
LED 1
Alarm mode
LED 2
Description
Section 3
Basic functions
Figure
13. The
Red
Green
Follow-S
Follow-F
Latched-S
LatchedAck-F-S
Programmable LED description
51

Advertisement

Table of Contents
loading