ABB RELION 611 Series Technical Manual page 54

Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

Section 3
Basic functions
48
Warnings are indicated with the text Warning additionally provided with the name
of the warning, a numeric code and the date and time on the LHMI. The warning
indication message can be manually cleared.
If a warning appears, record the name and code so that it can be
provided to ABB customer service.
Table 25:
Warning indications and codes
Warning indication
Warning
Watchdog reset
Warning
Power down det.
Warning
IEC61850 error
Warning
Modbus error
Warning
Dataset error
Warning
Report cont. error
Warning
GOOSE contr. error
Warning
SCL config error
Warning
Logic error
Warning
SMT logic error
Warning
GOOSE input error
Warning
GOOSE Rx. error
Warning
AFL error
Warning
Comm. channel down
Warning
Unack card comp.
Warning
Protection comm.
Further information on warning indications can be found in the operation manual.
Warning code
Additional information
10
A watchdog reset has occurred.
11
The auxiliary supply voltage has dropped
too low.
20
Error when building the IEC 61850 data
model.
21
Error in the Modbus communication.
24
Error in the Data set(s).
25
Error in the Report control block(s).
26
Error in the GOOSE control block(s).
27
Error in the SCL configuration file or the file
is missing.
28
Too many connections in the
configuration.
29
Error in the SMT connections.
30
Error in the GOOSE connections.
32
Error in the GOOSE message receiving.
33
Analog channel configuration error.
35
Redundant Ethernet (HSR/PRP)
communication interrupted.
40
A new composition has not been
acknowledged/accepted.
50
Error in protection communication.
1MRS757454 D
611 series
Technical Manual

Advertisement

Table of Contents
loading