Section 3
Basic functions
3.7.3
3.7.4
3.8
62
Authorization
By default, Test mode and Control mode can only be changed from LHMI. It is
possible to write test mode by remote client, if it is needed in configuration. This is
done via LHMI only by setting the Remote test mode parameter via Tests/IED test/
Test mode. Remote operation is possible only when control position of the relay is in
remote position. Local and remote control can be selected with R/L button or via
Control function block in application configuration.
When using the Signal Monitoring tool to force online values, the following
conditions need to be met.
•
Remote force is set to "All levels"
•
Test mode is enabled
•
Control position of the relay is in remote position
Table 40:
Remote test mode
Remote test mode
Off
Maintenance
All levels
LHMI indications
The yellow Start LED flashes when the relay is in "IED blocked" or "IED test and
blocked" mode. The green Ready LED flashes to indicate that the "IED test and
blocked" mode or "IED test" mode is activated.
Local/Remote control
Local/Remote control is realized through the R/L button on the front panel. Local/
Remote control supports control operations in substations according to the IEC 61850
standard.
By default, the relay supports station Authority level "L, R" and only local or remote
control access is allowed. Control access selection is made with R/L button.
61850-8-1-MMS
No access
Command originator category
maintenance
All originator categories
1MRS757454 D
WHMI/PCM600
No access
No access
Yes
611 series
Technical Manual