Technical Data - ABB RELION 611 Series Technical Manual

Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

Section 7
Measurement functions
7.1.5.6
366
Name
Type
U_INST_CA
FLOAT32
U_ANGL_CA
FLOAT32
U_DB_CA
FLOAT32
U_DMD_CA
FLOAT32
U_RANGE_CA
Enum
U_INST_A
FLOAT32
U_ANGL_A
FLOAT32
U_DMD_A
FLOAT32
U_INST_B
FLOAT32
U_ANGL_B
FLOAT32
U_DMD_B
FLOAT32
U_INST_C
FLOAT32
U_ANGL_C
FLOAT32
U_DMD_C
FLOAT32

Technical data

Table 413:
VMMXU Technical data
Characteristic
Operation accuracy
Suppression of harmonics
Values (Range)
Unit
0.00...4.00
xUn
-180.00...180.00
deg
0.00...4.00
xUn
0.00...4.00
xUn
0=normal
1=high
2=low
3=high-high
4=low-low
0.00...5.00
xUn
-180.00...180.00
deg
0.00...5.00
xUn
0.00...5.00
xUn
-180.00...180.00
deg
0.00...5.00
xUn
0.00...5.00
xUn
-180.00...180.00
deg
0.00...5.00
xUn
Value
Depending on the frequency of the voltage
measured: f
±2 Hz
n
At voltages in range 0.01...1.15 × U
±0.5% or ±0.002 × U
DFT: -50 dB at f = n × f
RMS: No suppression
1MRS757454 D
Description
U31 Amplitude,
magnitude of
instantaneous value
U31 angle
U31 Amplitude,
magnitude of reported
value
Demand value of U31
voltage
U31 Amplitude range
UL1 Amplitude,
magnitude of
instantaneous value
UL1 angle
Demand value of UL1
voltage
UL2 Amplitude,
magnitude of
instantaneous value
UL2 angle
Demand value of UL2
voltage
UL3 Amplitude,
magnitude of
instantaneous value
UL3 angle
Demand value of UL3
voltage
n
n
, where n = 2, 3, 4, 5,...
n
611 series
Technical Manual

Advertisement

Table of Contents
loading