ABB RELION 611 Series Technical Manual page 49

Hide thumbs Also See for RELION 611 Series:
Table of Contents

Advertisement

1MRS757454 D
Table 20:
IEC 61850-8-1 MMS settings
Parameter
Values (Range)
Unit mode
1) MMS client expects primary values from event reporting and data attribute reads
2) MMS client expects nominal values from event reporting and data attribute reads; this is the default for PCM600
3) For PCM600 use only, When
Nominal" and thus parameterizing in native form. The selection is not stored and is therefore effective only for one session. This value has
no effect if selected via the LHMI.
Table 21:
Modbus settings
Parameter
Values (Range)
Operation
1)
Port
Mapping selection
Address
Link mode
TCP port
Parity
Start delay
End delay
CRC order
Client IP
Write authority
Time format
Event ID selection
Event buffering
Table continues on next page
611 series
Technical Manual
Unit
1)
1=Primary
2)
0=Nominal
2=Primary-
3)
Nominal
Unit mode is set to "Primary", the PCM600 client can force its session to "Nominal" by selecting "Primary-
Unit
1=on
5=off
1=COM 1
2=COM 2
3=Ethernet - TCP 1
1...2
1...254
1=RTU
2=ASCII
1...65535
0=none
1=odd
2=even
0...20
0...20
0=Hi-Lo
1=Lo-Hi
0=Read only
1=Disable 0x write
2=Full access
0=UTC
1=Local
0=Address
1=UID
0=Keep oldest
1=Keep newest
Step
Default
0=Nominal
Step
Default
5=off
3=Ethernet - TCP
1
1
1
1
1
1=RTU
1
502
2=even
1
4
1
4
0=Hi-Lo
0.0.0.0
2=Full access
1=Local
0=Address
0=Keep oldest
Section 3
Basic functions
Description
IEC 61850-8-1 unit mode
Description
Enable or disable this protocol instance
Port selection for this protocol instance.
Select between serial and Ethernet based
communication.
Chooses which mapping scheme will be
used for this protocol instance.
Unit address
Selects between ASCII and RTU mode.
For TCP, this should always be RTU.
Defines the listening port for the Modbus
TCP server. Default = 502.
Parity for the serial connection.
Start delay in character times for serial
connection
End delay in character times for serial
connections
Selects between normal or swapped byte
order for checksum for serial connection.
Default: Hi-Lo.
Sets the IP address of the client. If set to
zero, connection from any client is
accepted.
Selects the control authority scheme
Selects between UTC and local time for
events and timestamps.
Selects whether the events are reported
using the MB address or the UID number.
Selects whether the oldest or newest
events are kept in the case of event buffer
overflow.
43