4.9.1. Setting of flow rate range

4.9.1.1. Setting of flow rate range (single range)

Description
 The range (full scale) of flow rate to be measured is set.
* The analog output (4-20mA) corresponds to the range setting.
 Settable range: 0.3 to 32 [m/s] in terms of flow velocity in piping
* The piping parameters and FLOW UNIT must be set beforehand.
* If a value beyond the settable range is inputted, "INPUT ERROR" appears and then last
setting is resumed.
* If "piping parameters" or "FLOW UNIT" has been changed after setting the range,
recommence the range setting.
<Note> The flow rate unit is as selected by "FLOW UNIT" in the "MEASURE SETUP" mode.
(Refer to Section 4.8.2.)
・ Setting range of the full scale frow rate
<Note>  Converted flow rate in the Table 1 is the calculation results obtained
by using the internal diameters of pipes in the left columns.
Perform calculation using the actual internal diameters for accuracy.
 Simple formula for calculation of flow verocity
For actual keying, refer to the typical operation indicated below. Set the protection to OFF beforehand. (See Section 4.4.1.)
Operation
Set the range type to single range and "FULL SCALE1" to flow rate 60m3/h.
(example)
* Set the piping parameters and "FLOW UNIT" beforehand.
Key operation
Press the
Press the
ENT
Press the
Press the
ENT
Because flow rate (factory set) is already registered, go to the next step
Press the
Because single range (factory set) is already registered, go to the next
step.
Press the
Press the
ENT
Move the cursor by the
key.
Change the full scale1 to "60".
Note) To change the decimal point position, align the cursor with a place
to change to and press the
Press the
ENT

4.9. Output Setting

Description
key twice to display "OUTPUT SETUP".
key to enter the "ZERO ADJUSTMENT" mode.
ENT
key for 4 times to display "RANGE".
key once to display "KIND".
ENT
"RANGE TYPE"
key to display
key once to display "FULL SCALE1".
key once to blink the cursor.
ENT
key, and change the numeric value by the
key once to register.
ENT
――― FULL SCALE1 has been registered. ―――
Flow velocity range:
Int. dia.
of pipes
[mm]
100
150
200
300
key likewise.
-33-
20mA
Full scale 1
4mA
0
Flow rate
0.3
32 [m/s]
Flow rate unit
3
[ m
/h ]
25
0.530 to 56.5
50
2.12 to 226
80
5.43 to 579
8.48 to 905
19.1 to 2036
33.9 to 3619
76.3 to 8143
Display
OUTPUT SETUP
ZERO ADJUSTMENT
RANGE
KIND
RANGE TYPE
FULL SCALE1
FULL SCALE1
FULL SCALE1
0000060.0
FULL SCALE1
 COMPLETE 
FULL SCALE1
100%
<Table1>
[ L/min ]
8.84 to 942
35.3 to 3770
90.5 to 9651
141 to 15080
318 to 33929
565 to 60319
1272 to 135717
SET ZERO
FLOW RATE
SINGLE
15.000 m3/h
00015.000 m3/h
00015.000 m3/h
00065.000 m3/h
00065.000 m3/h
m3/h
60.000 m3/h