Output Setting (For External Power Supply Type) - Fuji Electric FWD Series Instruction Manual

Ultrasonic flowmeter for air
Table of Contents

Advertisement

3-2. Output setting (for external power supply type)

Unit of output pulse
Open drain output 2
Current output
It is recommended that the setting of the flow meter be carried out before installation.
Current output [F15]
One of three output forms of instantaneous flow-rate, pressure and temperature can be
selected for the current output to suit your usage.
When the instantaneous flow-rate is selected, electric current corresponding to the setting of
the maximum flow-rate value of the analog output is outputted.
When the pressure is selected, 4 mA is outputted at the atmospheric pressure, and 20 mA is
outputted at 1 MPa.
When the temperature is selected, 4 mA is outputted at -10C, and 20 mA is outputted at
+60C.
Maximum flow-rate value of the analog current output (Analog output FS flow-rate) [F2]
When the analog output is used by setting to the instantaneous flow-rate, it is recommended
that full scale flow-rate (FS flow-rate) of the analog current output be set with a value
corresponding to maximum flow-rate used.
It is recommended that a numerical value having a margin be set as a set value of the FS
flow-rate.
(Setting example of the FS flow-rate: A set value at the time of nominal diameter 50mm,
flow-rate conversion "With(ON)", room temperature (30°C), pressure 0.7 MPa, flow speed
3
10m/s: 600 m
/h)
Output settings 
F9
Output pulse unit
F4
Contact output
Instantaneous 
F15 
Current output
Temperature
14
Pulse output
(reverse flow)
Alarm output
Alarm judgment value
flow‐rate
Analog output FS flow‐rate
Pressure
F3 
Alarm output
F5
Lower limit alarm  
F6 
Upper limit alarm
F7 
F2 

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents