Optional) Charging In Refrigerant Oil - Huawei NetCol5000-A035 User Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A035:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
Refrigerant Oil
The refrigerant oil, Danfoss 160SZ, is recommended.

5.2.2 (Optional) Charging in Refrigerant Oil

Prerequisites
Refrigerant oil is prepared by referring to
the Refrigerant and Refrigerant
Procedure
Step 1 Connect the refrigerant oil bucket, pressure gauge, and vacuum pump to the
device, as shown in
Issue 17 (2020-10-22)
If the indoor unit code is one of 52270741, 52270742, 52270743, 52270744,
52270745, 52270746, 52270747, and 52270748, additional refrigerant oil =
additional refrigerant charge x 2.5%.
If no, charge refrigerant oil as follows:
If the low-temperature component is not connected, do not add
refrigerant oil.
If the low-temperature component is connected, and L ≤ 10 m, do not
add refrigerant oil.
If the low-temperature component is connected, and L > 10 m, additional
refrigerant oil = additional refrigerant charge x 4%.
Figure
Copyright © Huawei Technologies Co., Ltd.
5.2.1 Calculation about the Charged
Oil.
5-1.
5 Power-On Commissioning