NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
Item
Airflow
Air filter
Dimensions (H x D x
W)
a: Indoor dry-bulb temperature: 37.8°C. Wet-bulb temperature: 20.8°C.
Condensing temperature: 45°C.
b: Frames can be used to expand the depth to 1200 mm, while top supports can
be used to top frame to 2200 mm.
● When the total load of servers, relative to a single smart cooling product, is less
than 10 kW, smart cooling products that have heating and humidification
functions or partial heating and humidification functions are recommended.
● The condensate pump is mandatory for scenarios where pipes are routed from
the top or if it is required by the customer.
Table 2-9 Optional Parameters of NetCol5000-A035
Item
Max Current
Condensate
pump
Reheat
Humidify
Reheating
capacity
Humidifying
capacity
Issue 17 (2020-10-22)
NetCol5000-A035
6800 m
G4 filter
2000 mm x 600 mm x
1100 mm
b
NO TICE
NetCol5000-
A035H512D2
E120E1
32 A
Yes
Yes
Yes
6.0 kW
3.0 kg/h
Copyright © Huawei Technologies Co., Ltd.
3
/h
NetCol5000-
NetCol5000-
A035H512D2
A035H512D2
E120E0
0020E1
32 A
26 A
No
Yes
Yes
No
Yes
No
6.0 kW
N/A
3.0 kg/h
N/A
2 Product Description
NetCol5000-A025
3
4600 m
/h
G4 filter
2000 mm x 600 mm x
1100 mm
NetCol5000-
A035H512D2
0020E0
26 A
No
No
No
N/A
N/A
22