Huawei NetCol5000-A035 User Manual page 91

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A035:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
● RS485_R must be switched to OFF.
● After the address is set, choose Settings > System Settings > T/H Sensor on
the home page after power-on and set the sensors in the aisle corresponding to
the address to Enable. Otherwise, the sensors will not work.
Table 3-17 DIP switch operation description
Position
Return
air side
Cold
aisle
Hot
aisle
Issue 17 (2020-10-22)
NO TICE
Name
Temperature
and humidity
1 at the
return air
vent
Temperature
and humidity
1 at the cold
aisle
Temperature
and humidity
2 at the cold
aisle
Temperature
and humidity
3 of the cold
aisle
Temperature
and humidity
1 at the hot
aisle
Temperature
and humidity
2 at the hot
aisle
Temperature
and humidity
3 at the hot
aisle
Copyright © Huawei Technologies Co., Ltd.
Address
DIP Switch ID
1
2
1
ON
OFF
11
ON
ON
12
OFF
OFF
13
ON
OFF
21
ON
OFF
22
OFF
ON
23
ON
ON
3 Installation Guide
3
4
5
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
6
OFF
OFF
OFF
OFF
OFF
OFF
OFF
81

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-a025

Table of Contents