Step 9 Blow away dirt with nitrogen.
Step 10 Replace the dryer filter.
When replacing the dryer filter, take measures to protect pipes from foreign
matter.
Step 11 Install a new compressor, crankcase heat tape, and dryer filter in the steps of
10
to
refrigerant. For details, see section 5.2 Vacuumizing and Charging in Refrigerant.
Install and tighten the corner valve on discharge pipe to a torque of 100 N m with
a torque wrench, and tighten the corner valve on suction pipe to a torque of 120
N m.
Step 12 Connect the compressor cable and check that the phase sequences are correct.
Then choose Maint > Diagnostic Mode > Enter to check the system pressure and
temperature and ensure the refrigerant is charged with an optimal system status
(see 5.5 Commissioning Procedure).
Step 13 On the main screen, choose Maint > Performance Maint, clear up the compressor
running time.
----End

6.5.4 Replacing the High Pressure Switch

Prerequisites
Context
The high pressure switch can be maintained only from the rear.
Procedure
Step 1 On the controller home screen, tap Shutdown, and turn off the smart cooling
product switch in the upstream PDC.
Issue 17 (2020-10-22)
CA UTION
Step
1. Vacuumize the system and partially charge the system with
CA UTION
The high pressure switch needs to be replaced.
A spare high pressure switch of the same model is available and functional.
Tools: gloves, Two adjustable wrenchs, thread sealant
NO TE
The procedure for replacing a high or low pressure sensor is similar to that for replacing the
high pressure switch.