Huawei NetCol5000-A035 User Manual page 179

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A035:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
Al
ar
m
ID
a0
33
a0
34
a0
35
Issue 17 (2020-10-22)
Alar
Alar
Defau
m
m
lt
Seve
Value
rity
Powe
MAJ
-
r
OR
phas
e C
unde
rvolt
Powe
MAJ
-
r
OR
overf
req
Powe
MAJ
-
r
OR
unde
rfreq
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Impac
Possible Cause
t
The
1. The power
alarm
supply voltage is
is
lower than the
genera
power undervolt
ted,
alarm thres.
and
2. If a voltage
the
jumper is used,
system
possibly it is
shuts
incorrectly
down.
connected.
3. If a toggle
switch is used,
possibly it is
incorrectly set.
The
1. The power
alarm
supply frequency
is
is too high.
genera
2. The SPD three-
ted,
phase test board
and
is faulty.
the
system
shuts
down.
The
1. The power
alarm
supply frequency
is
is too low.
genera
2. The SPD three-
ted,
phase test board
and
is faulty.
the
system
shuts
down.
Solution
1. Check the
power supply
voltage.
2. Maintain or
replace the
voltage jumper.
3. Correctly set the
toggle switch.
1. Check the
power supply
frequency.
2. Replace the SPD
three-phase test
board.
1. Check the
power supply
frequency.
2. Replace the SPD
three-phase test
board.
169