NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
Compon
ent
Humidit
y and
tempera
ture
sensor
Water
sensor
Compressor Oil Level
You can view the refrigerant oil status from the oil sight glass of the compressor.
Figure 5-6
Water Sensor
When the pair of terminals of the water sensor detect water or other conductive
liquid, resistance between the two terminals decreases. During the maintenance,
check that the two detection terminals, as shown in
corrosion, foreign matter, and connection in between.
Figure 6-2 Water sensor detection terminals
(1) Detection terminals
6.2.5 Quarterly Maintenance
Table 6-4
Issue 17 (2020-10-22)
Item
Humidity and temperature
sensors in smart cooling
products and aisles are
securely installed.
The water sensor is secure,
and the two downward metal
conductive plates do not
interfere with each other or
corrode.
shows the normal and abnormal refrigerant oil states.
lists quarterly maintenance items for the indoor unit.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Troubleshooting
Secure the sensors again by
referring to
3.11.6 Installing a
Humidity and Temperature Sensor
Outside the
Cabinet.
Replace the water sensor by
referring to
3.11.4 Connecting the
Signal
Cables.
Figure
6-2, are free from
157