Huawei NetCol5000-A035 User Manual page 106

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A035:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
Procedure
Step 1 Choose Settings > Comm Settings > Modbus Settings on the home page. The
page shown in
Figure 4-10 Setting Modbus communications parameters
Step 2 Set the parameters by following instructions in
Table 4-5 Modbus parameter settings
Parameter
Protocol
Baud rate
Comm
address
Issue 17 (2020-10-22)
product can be connected only to an EMS with a specific ID address. If
Connection mode is set to Server+client, one smart cooling product can be
accessed by a maximum of two EMS clients and connect to an EMS with a
specific ID address at the same time.
Figure 4-10
Specification
Modbus RTU,
Modbus TCP
9600, 19200
1–255
Copyright © Huawei Technologies Co., Ltd.
is displayed.
Table
Setting Method
● Modbus RTU: If a smart cooling product needs
to connect to an EMS using an RS485 cable, set
Protocol to Modbus RTU.
● Modbus TCP: If a smart cooling product needs
to connect to an EMS through an IP address
network, set Protocol to Modbus TCP.
Set the baud rate as required. The value should be
consistent with that at the EMS side. This
parameter is configurable when Protocol is set to
Modbus RTU.
Set the address of the smart cooling product. The
EMS communicates with the smart cooling product
through this address, and the addresses of two
smart cooling products connected to the same
EMS must be unique. This parameter is
configurable when Protocol is set to Modbus RTU.
4 ACC Introduction
4-5.
96