NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
Parameter
Temp control
mode
Supply-air
temp set point,
Supply-air
humid set
point
Return-air
temp set point,
Return-air
humid set
point
Cold-aisle
temp set point,
Cold-aisle
humid set
point
Hot-aisle temp
set point, Hot-
aisle humid set
point
Cold aisle
sensor 1, 2, 3
Hot aisle
sensor 1, 2, 3
----End
Issue 17 (2020-10-22)
Description
Controls the
temperature inside
the room or aisles
based on the
Average,
Maximum, or
Minimum of the
temperatures
collected by each
sensor.
Sets the required
humidity and
temperature in a
room or aisle.
Sets the sensors in
cold aisles to
Enable.
Sets the sensors in
hot aisles to
Enable.
Copyright © Huawei Technologies Co., Ltd.
Configuration Principle
● Average: Select Average if the
temperature is to be controlled based
on the averaged data value collected
by the collector.
● Maximum: Select Maximum if the
temperature is to be controlled based
on the maximum data value collected
by the collector.
● Minimum: Select Minimum if the
temperature is to be controlled based
on the minimum data value collected
by the collector.
The ACC controls the temperature and
humidity based on the set value. For
example, if Temp control type is set to
Return-air, Return-air temp set point
is set to 30.0, and Return-air humid set
point is set to 25.0, the ACC will control
the temperature and humidity around
the return-air vent of the smart cooling
product to a temperature of 30°C and
humidity of 25% RH.
Enable the corresponding humidity and
temperature sensor installed in the cold
aisle.
Enable the corresponding humidity and
temperature sensor installed in the hot
aisle.
4 ACC Introduction
94