Exercise caution because the device is still energized after it is shut down on the
controller home screen.
Step 2 Open the rear door and remove the air filter.
Step 3 Remove the cables from the high pressure switch.
Figure 6-8 Position of the high pressure switch
Step 4 Secure the pipe nut using an adjustable wrench, and loosen the adjustable nut
using another adjustable wrench until the high pressure switch is removed.
Figure 6-9 Removing a high pressure switch
(1) Pipe nut
Exercise caution when removing the high pressure switch because a small amount
of refrigerant will be sprayed when you remove the switch.