NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
Ports
Table 2-5
Table 2-5 Ports
Port
Refrigerant liquid
pipe
Refrigerant gas pipe
Pump drainpipe
Humidifier water
supply pipe
Condensate self-
drainpipe
Figure 2-6 Screw thread connector
Installation requirements
Table 2-6
When the total load of servers, relative to a single smart cooling product, is less
than 10 kW, the humidity might be relatively high. It has no relationship with
product quality, and you are recommended to install a dehumidifier.
Issue 17 (2020-10-22)
describes the ports on the NetCol5000-A.
NO TE
BSPP 1/2 inch: Large diameter: 20.955 mm; medium diameter: 19.793 mm; small diameter:
18.631 mm; medium diameter tolerance: 0–0.142 mm; small diameter tolerance: 0–0.541
mm.
describes the installation requirements of NetCol5000-A.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
Description
Flaring copper pipe inner diameter: 5/8 inch, soldered.
Flaring copper pipe inner diameter: 7/8 inch, soldered.
Reserved: 1/2 inch BSPP (British Standard Pipe Parallel)
screw thread connector, as shown in
Reserved: 1/2 inch BSPP screw thread connector, as
shown in
Figure
2-6.
Reserved: 1/2 inch BSPP screw thread connector, as
shown in
Figure
2-6.
2 Product Description
Figure
2-6.
19