NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
----End
4.7.10 Which Parameters Are Restored to Default Values After
Default Settings Are Operated
After choosing Settings > Restore Defaults > Yes, the following parameters are
displayed:
To prevent loss of important data, record all parameter values before restoring
default settings. After restoring default settings, change the parameter values to
the recorded values.

4.7.11 How to Change the SSH Access Password

Context
Issue 17 (2020-10-22)
NO TE
● Master/Slave and Active/Standby indicate the information of this single unit. Other
information is about the teamwork control information of the group.
● Required cooling capacity: indicates the total cooling/heating requirements of the group
and is used as a reference for enabling the cooling/heating mode by the master device.
If the cascade function is enabled, the capacity is used as a reference for determining
whether to start a standby unit.
● Required humidity: indicates the total dehumidification and humidification requirements
of the group and is used as a reference for enabling the dehumidification and
humidification mode by the master device.
All parameters displayed on Settings > System Settings.
All parameters displayed on Settings > Alarm Settings.
All parameters displayed on Settings > Comm Settings.
Date format and time zone settings displayed on Settings > User Settings.
All parameters displayed on Maint > Sensor Adjust.
NO TICE
NO TE
After default settings are restored, all communication addresses are changed to 1 and the
communication between all devices and the EMS is disconnected. The communication
addresses must be reset to recover the communication.