Huawei NetCol5000-A035 User Manual page 168

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A035:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
Table 6-4 Quarterly maintenance checklist
Compon
ent
Monitori
ng
Humidifi
er
Issue 17 (2020-10-22)
Item (on the Basis of
Monthly Maintenance)
Export smart cooling product
logs, alarms, temperatures,
humidity, the operating status
of the compressor, fan,
electric heater, electric
humidifier, and water pump,
and time from the monitoring
system. View the historical
alarms generated in this
quarter and select the most
common five ones. (If no
monitoring system is
available, skip this item.)
Start the indoor unit, choose
Maint > Diagnostic Mode >
Enter from the main screen,
and set Humidifier to 50%.
Water injection is smooth.
(Following the preceding
step) Set Humidifier to 0%,
and press the manual water
drain button on the side of
the electric control box to
check whether water drainage
is normal. After the check is
complete, set the manual
drainage button on the side
of the electric control box to
normal humidification.
NOTE
1. Ensure that the manual
drainage button on the side
of the electric control box is
set to "O: Normal
humidifying" after the check
ends. Otherwise, the
humidifier will not be filled
with water when it is
running.
2. If the humidifier cylinder is
dirty and the water level
exceeds 4/5 during the
quarterly maintenance,
replace the cylinder.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Troubleshooting
Rectify the fault or contact Huawei
technical support.
● Check that the water inlet sluice
is open.
● Disconnect the humidifier water
injection hose and clear the
blockage in the hose.
Disconnect the drainpipe from the
device, and use a rubber mallet to
knock the drainpipe to remove
foreign matter or impurities from
the drainpipe. Then remove the
water pump and clean up
impurities from the water pump. If
the impurities are too much to be
cleared, replace the water pump.
NOTE
● When installing a pipe, seal screw
thread joints using water sealant
and ensure that no water leaks.
● If the fault persists after the
maintenance, see section
Troubleshooting
for further
processing.
6.4