Figure 6-21 Replacing the humidifier cylinder
Step 4 Loosen the belt around the humidifier cylinder and remove the cylinder, as shown
by (2) and (3) in
Step 5 Open the rubber pad on the cable port, and clear the glue on the port using a
flat-head screwdriver, as shown by (4) in
Step 6 Remove the screws from the electrode cable connection terminals above the
humidifier cylinder using the 10# socket wrench, remove the cable connection
terminals, and remove the cable from the high water level sensor, as shown by (5)
in
Figure
Step 7 Install a new humidifier cylinder by performing
order, and start the humidifier.
Step 8 Power on the humidifier, choose Maint > Diagnostic mode on the main menu,
and enter 100%. The water is injected to the humidifier. Check whether the
humidifier works properly. If yes, exit the diagnostic mode.
Issue 17 (2020-10-22)
Figure
6-21.
6-21.
NO TE
When replacing the humidifier cylinder, you do not need to apply glue to the cable
connection port again.
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Figure
6-21.
Step 3
to
Step 6
in the reverse
221