Figure 4-50 Message 2
Procedure
Step 1 Check whether strong electromagnetic interference exists around the E-label
identification board.
Step 2 Disconnect the power supply of the smart cooling product.
Step 3 Check whether the E-label identification board is properly connected.
Step 4 Check whether cables are properly connected.
Step 5 Reconnect the power supply of the smart cooling product.
Step 6 If the fault persists, contact Huawei technical support.
----End
Issue 17 (2020-10-22)
If the information shown in
the smart cooling product cannot run properly. Perform
subsequent steps.
NO TE
In the
Figure 4-50
the ACC V100R001C20SPC300 version is used as an example to describe
the WebUI prompt messages. During actual operations, the version in use prevails.
If yes, contact Huawei technical support.
If no, continue with
Step
If no, reconnect the board properly and continue with
If yes, continue with
If yes, contact Huawei technical support to replace the E-label identification
board.
If no, reconnect or replace cables and perform