Removing The Transport Fasteners From The Compressor - Huawei NetCol5000-A035 User Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A035:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
The wiring terminals must stay in good contact with the floats. Otherwise, the
condensate pump cannot start properly.
Figure 3-13 Removing the transport fasteners from the floats and connecting the
wiring terminals
----End

3.4.2 Removing the Transport Fasteners from the Compressor

Context
When removing transport fasteners, do not remove the fuel return solenoid valve.
Otherwise, the solenoid valve might be burnt due to improper reinstallation.
Procedure
Step 1 Loosen the three bolts on the compressor using a 13# solid wrench, as shown in
Figure
Do not directly take the bolts out.
Step 2 Remove the transport fasteners.
Issue 17 (2020-10-22)
CA UTION
NO TE
● The wiring terminal to the low float has been factory installed.
● Put away the removed rubber fixing objects. If the container is to be transported again,
remove the wiring terminal from the high float and reinstall them.
CA UTION
3-14.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
3 Installation Guide
41

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-a025

Table of Contents