NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
The wiring terminals must stay in good contact with the floats. Otherwise, the
condensate pump cannot start properly.
Figure 3-13 Removing the transport fasteners from the floats and connecting the
wiring terminals
----End
3.4.2 Removing the Transport Fasteners from the Compressor
Context
When removing transport fasteners, do not remove the fuel return solenoid valve.
Otherwise, the solenoid valve might be burnt due to improper reinstallation.
Procedure
Step 1 Loosen the three bolts on the compressor using a 13# solid wrench, as shown in
Figure
Do not directly take the bolts out.
Step 2 Remove the transport fasteners.
Issue 17 (2020-10-22)
CA UTION
NO TE
● The wiring terminal to the low float has been factory installed.
● Put away the removed rubber fixing objects. If the container is to be transported again,
remove the wiring terminal from the high float and reinstall them.
CA UTION
3-14.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
3 Installation Guide