NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
Al
ar
m
ID
a0
51
a0
52
a0
55
Issue 17 (2020-10-22)
Alar
Alar
Defau
m
m
lt
Seve
Value
rity
Hot-
Critic
45°C
aisle
al
HT
Supp
Majo
N/A
ly-air
r
1
temp
invali
d
Supp
ly-air
2
temp
invali
d
Supp
ly-air
3
temp
invali
d
Disch
Majo
N/A
arge
r
temp
sens
or
fault
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Impac
Possible Cause
t
The
1. The hot-aisle
alarm
T/H sensors are
is
located in
genera
inappropriate
ted,
position.
and
2. The ambient
the
temp is high.
rotatio
3. The hot-aisle HT
nal
alarm thres is
speed
inappropriate.
of the
4. The temp
compr
displayed is
essor
different from
increas
the actual temp.
es.
5. The load is high
or the
refrigeration
capacity is
insufficient.
The
1. The cables to the
alarm
temp sensor are
is
loose or
genera
damaged.
ted.
2. The temp sensor
is faulty.
The
1. The cables to the
alarm
temp sensor are
is
loose or
genera
damaged.
ted.
2. The temp sensor
is faulty.
Solution
1. Adjust the
position of the
hot-aisle T/H
sensors.
2. Check the
ambient temp.
3. Adjust the hot-
aisle HT alarm
thres.
4. Calibrate or
replace the
abnormal T/H
sensors.
5. Add more smart
cooling product
units.
1. Check the
cables to the
temp sensor.
2. Maintain or
replace the
temp sensor.
1. Check the
cables to the
temp sensor.
2. Maintain or
replace the
temp sensor.
175