NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
Temperatur
e (ºC)
7
8
9
10
11
12
13
14
15
16
17
18
3.2.2 Refrigerant Oil RB75EA
The refrigerant oil is RB75EA. A sufficient amount of refrigerant oil has been filled
in the indoor compressor before delivery to ensure the reliable running of a 60 m
long pipe. Additional refrigerant oil is not required during onsite installation. When
the compressor is damaged, refrigerant oil has been filled in the compressor
before the compressor is replaced. Additional refrigerant oil is not required during
replacement. Add refrigerant oil based on the actual situation only when the
refrigerant oil leaks and the compressor does not need to be replaced.
3.2.3 Pipe
Oil Trap
Figure 3-2
Issue 06 (2022-11-25)
Saturation
Temperatu
Pressure –
re (ºC)
Gauge
Pressure
(MPa)
0.9
26
0.93
27
0.96
28
0.99
29
1.02
30
1.05
31
1.09
32
1.12
33
1.16
34
1.19
35
1.23
36
1.27
37
shows the oil trap specifications.
Copyright © Huawei Technologies Co., Ltd.
Saturation
Temperatu
Pressure –
re (ºC)
Gauge
Pressure
(MPa)
1.60
45
1.65
46
1.69
47
1.74
48
1.79
49
1.84
50
1.89
51
1.94
52
1.99
53
2.04
54
2.1
55
2.15
–
3 Installation
Saturatio
n
Pressure –
Gauge
Pressure
(MPa)
2.63
2.7
2.76
2.83
2.9
2.97
3.04
3.11
3.19
3.26
3.34
–
30