Figure 4-13 Teamwork configuration reference
Follow-up Procedure
After you have completed the settings, check whether the teamwork networking is
successful by performing the following steps:
1.
2.
3.
4.
Issue 17 (2020-10-22)
NO TE
RS485 only: Units under CAN teamwork must be free from CAN cables in between. You
need to prepare cables that support only RS485 communication. For how to make cable
crimp terminals, refer to the section of teamwork networking and monitoring.
Check whether the device number on the topology is the same as the actual
device number.
If yes, go to 2.
If no, check the cable connection and the settings of teamwork control
parameters.
Check whether the number of the running devices on the topology is the
same as the actual device number.
If yes, go to 3.
If no, check the cable connection and the settings of teamwork control
parameters.
Check whether the number of backup devices on the topology is the same as
the actual device number.
If yes, go to 4.
If no, check the cable connection and the settings of teamwork control
parameters.
Check whether the number of online devices on the topology is the same as
the actual device number.