NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
Procedure
Step 1 On the home screen, choose Maint > Sensor Adjust.
Figure 4-35 Sensor adjust screen
Step 2 Fill the calibration value based on the measured error.
----End

4.6.2.6 Calibrating the Screen

Context
● You can calibrate the screen by DIP switch only when the system enters Quick
Settings page after the first power-on or when the system is on the home
screen.
● Touch the LCD screen firmly if you are using your fingertips. It is recommended
that you use the pen tip for accurate selection and quick response.
● After the DIP switch is calibrated, flip toggle switch 1 to ON, and others to the
opposite position.
Issue 17 (2020-10-22)
To calibrate a sensor, log in as the Admin or Engineer user.
You can calibrate for touching point deviation on the touchscreen.
You can calibrate the screen by tapping the screen on the Screen Calib page
or by DIP switch.
Tapping the screen on the screen calib page: The program of the display
board works normally; the deviation between the touching point and the
responding point is small; the Maint > Screen Calib page can be entered
over the screen.
Calibrating the screen by DIP switch: The display board works normally;
the deviation between the touching point and the responding point is
unfavorably big; or the screen does not respond when being tapped.
To calibrate the touchscreen, log in as the Admin or Engineer user.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
4 ACC Introduction
Figure 4-35
is displayed.
120