NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
Figure 3-11 Position of the water tank
(1) Water pan
Figure 3-12 Positions of high and low floats
(1) High floats
Procedure
Step 1 Loosen the two butterfly nuts from the high and low floats in the water tank, and
remove the transport fasteners for the floats.
Step 2 Secure the butterfly nuts.
Step 3 Connect the wiring terminals to the high float. The wiring terminals must be fixed
higher than the water pan. Otherwise, water may drop into the wiring terminals.
Issue 17 (2020-10-22)
(2) Water tank
Copyright © Huawei Technologies Co., Ltd.
(3) High and low floats
(2) Low floats
3 Installation Guide