Huawei NetCol5000-A035 User Manual page 180

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A035:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
Al
ar
m
ID
a0
36
a0
37
a0
38
a0
39
Issue 17 (2020-10-22)
Alar
Alar
Defau
m
m
lt
Seve
Value
rity
Powe
Critic
N/A
r
al
phas
e
loss
Powe
CRITI
-
r
CAL
phas
e
rever
se
Liqui
MAJ
-
d
OR
pipe
temp
sens
or
fault
Ctrl
Majo
N/A
point
r
sens
or
disab
led
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Impac
Possible Cause
t
The
1. The power grid
alarm
is unstable.
is
2. The surge
genera
protection board
ted,
is faulty if
and
configured.
the
3. The main power
system
supply or the
shuts
comp driver
down.
supply is
connected
improperly.
The
1. The power grid
alarm
is unstable.
is
2. The surge
genera
protection board
ted,
is faulty.
and
the
system
shuts
down.
The
1. Cables to the
alarm
liquid pipe temp
is
sensor are not
genera
properly
ted.
connected.
2. The liquid pipe
temp sensor is
faulty.
The
All the T/H sensors
alarm
of the control point
is
are disabled.
genera
ted,
and
the
system
shuts
down.
Solution
1. Check the
power grid.
2. Maintain or
replace the
surge protection
board.
3. Check the main
power supply or
cables to the
comp driver.
1. Check the
power grid.
2. Maintain or
replace the
surge protection
board.
1. Maintain or
replace the
liquid pipe temp
sensor.
2. Check cables to
the liquid pipe
temp sensor.
Enable the T/H
sensors of the
control point or
change the control
point.
170