Huawei NetCol5000-A035 User Manual page 44

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A035:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
Table 3-10 Cable specifications
Name
Indoor unit
power
cable
Outdoor
unit power
cable
Voltage
jumper
Outdoor
unit on/off
signal
cable
Water
sensor
signal
cable
Teamwork
networkin
g cable
Humidity
and
temperatu
re sensor
and its
cable
a: If you use a five-core cable, do not install the neutral wire (blue). Instead, cut
off it and properly wrap PVC insulation tape around the cutting place. Purchase
indoor unit power cables with qualified diameters (16.8–18 mm). Otherwise, the
power cables will fail to be routed through the clip.
Issue 17 (2020-10-22)
Specifications
a
Four-core cable
: electrical power
cable-600 V/1000 V-ZA-RVV-6 mm
A
L1, L2, and L3 terminals: common
terminal-single cord end terminal-6
2
mm
-0.02 m-30 A-inserted depth 12
mm
PE terminals: naked crimping terminal-
2
OT-6 mm
-M6-50 A-tin plated-12 AWG
to 10 AWG
For detail cable specifications, see the
outdoor unit user manual.
Six voltage jumpers are available in the
fitting bag. Select one for use.
For details about the cable
specifications, see the outdoor unit user
manual.
Power cable-5m-22AWG-(2 x T0.5
x 22UL1007)-(2 x T0.5
It also can be used for host monitoring.
N/A
Copyright © Huawei Technologies Co., Ltd.
Quantity
1 PCS (The
length is
2
-46
determine
d in
presale
survey.)
6 PCS
2 PCS
1 PCS
1 PCS
1 PCS
1 PCS
2
)-(2
2
)
1 PCS
(10m)
Max 6 PCS
3 Installation Guide
Remarks
Optional
Mandatory
Mandatory
Optional
Mandatory
Optional
Mandatory
Mandatory