Huawei NetCol5000-A035 User Manual page 177

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A035:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
Al
ar
m
ID
a0
26
a0
27
a0
28
a0
29
Issue 17 (2020-10-22)
Alar
Alar
Defau
m
m
lt
Seve
Value
rity
Air
Warn
4320
filter
ing
hours
excee
d
runti
me
Powe
Warn
N/A
r loss
ing
Powe
MAJ
-
r
OR
phas
e A
overv
olt
Powe
MAJ
-
r
OR
phas
e B
overv
olt
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Impac
Possible Cause
t
The
The accumulated
alarm
runtime of the air
is
filters exceeds the
genera
alarm thres.
ted.
The
The supply power is
alarm
cut off.
is
genera
ted.
The
1. The power
alarm
supply voltage is
is
higher than the
genera
power overvolt
ted,
alarm thres.
and
2. If a voltage
the
jumper is used,
system
possibly it is
shuts
incorrectly
down.
connected.
3. If a toggle
switch is used,
possibly it is
incorrectly set.
The
1. The power
alarm
supply voltage is
is
higher than the
genera
power overvolt
ted,
alarm thres.
and
2. If a voltage
the
jumper is used,
system
possibly it is
shuts
incorrectly
down.
connected.
3. If a toggle
switch is used,
possibly it is
incorrectly set.
Solution
Maintain or
replace the air
filters. Tap Maint >
Performance
Maint to clear the
accumulated
runtime.
Check the power
supply cables.
1. Check the
power supply
voltage.
2. Maintain or
replace the
voltage jumper.
3. Correctly set the
toggle switch.
1. Check the
power supply
voltage.
2. Maintain or
replace the
voltage jumper.
3. Correctly set the
toggle switch.
167