Setting Temperature And Humidity Values - Huawei NetCol5000-A035 User Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A035:
Table of Contents

Advertisement

NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
Figure 4-7 Start and shutdown
----End

4.5.2.3 Setting Temperature and Humidity Values

Context
To set T/H control type, Temp control mode, cold aisle sensors 1, 2, and 3, and
hot aisle sensors 1, 2, and 3, log in as the Admin or Engineer user. To set other
parameters, log in as the Admin, Engineer, or Operator user.
Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H Sensor.
4-8
Issue 17 (2020-10-22)
NO TE
● If a power failure occurs and the smart cooling product is powered on again, the smart
cooling product automatically restores to the original state (start or shutdown) before
the power failure.
● The hardware port for controlling the status of the remote dry contact or On/Off
status on remote is reserved on the ACC. The status of the remote dry contact and
On/Off status on remote is on by default.
● The operations that start the smart cooling product successfully by the LCD button or by
element management system (EMS) is effective only when the remote dry contact or
On/Off status on remote is on the status of on.
● In start mode, the Start button is green (unavailable) and the Shutdown button is gray
(available).
● In shutdown mode, the Shutdown button is green (unavailable) and the Start button is
gray (available).
is displayed.
Copyright © Huawei Technologies Co., Ltd.
4 ACC Introduction
Figure
92

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-a025

Table of Contents